Spread foundations refer to foundation components that transfer their loads to the subsoil only by normal stresses and shear stresses. Spread foundations are single foundations, strip foundations, or raft foundations. The requirement for spread foundations is the bearing capacity of the subsoil below the bottom of the foundation. If the subsoil has insufficient bearing capacity, improvement to the subsoil or alternative foundation systems are required.
Spread foundations refer to foundation components that transfer their loads to the subsoil only by normal stresses and shear stresses. Spread foundations are single foundations, strip foundations, or raft foundations. The requirement for spread foundations is the bearing capacity of the subsoil below the bottom of the foundation. If the subsoil has insufficient bearing capacity, improvement to the subsoil or alternative foundation systems are required.
Basically, the depth of the foundation level is specified to facilitate a frost-free foundation. In Germany, this is at least 80 cm below the surface. Information on the different regional frost penetration depths is contained in [1–3].
The following incidents have to be avoided during the preparation of the foundation level:
Before the installation of the blinding concrete, the foundation level has to be checked by a geotechnical expert.
For the excavation of single loads like columns, single foundations are used. Strip foundations are used for line loads. Both types of spread foundation can be designed with or without a reinforcement, whereby reinforced foundations should be preferred due to their greater robustness. Figure 3.1 shows the two types of foundations.
Generally, the design of single and strip foundations based on the contact pressure is sufficient. In most cases, the contact pressure can be determined by the stress trapeze method. Deformations of the subsoil and the building, as well as the soil–structure interaction, are not taken into account.
Figure 3.1 Single and strip foundation.
Raft foundations are used when the load grid is dense and the deformations of the subsoil and the construction have to be homogenized. Raft foundations can be used as a part of a so-called white trough, or in combination with an additional sealing system (e.g., bitumen layers) to prevent ground-water influx [4–7].
The thickness of the reinforcedconcrete slab depends on the bending moment, as well as on the punching (concentrated loads). Increasing the slab thickness or arranging concrete haunches can avoid shear reinforcements. To prevent groundwater influx or to repel weather conditions, the crack width of the concrete has to be limited. In any case, the installation of construction joints, expansion joints and settlement joints has to be planned precisely and supervised during the construction phase.
Two different theoretical models are used for the geotechnical analysis of the SLS and the ULS. For the analysis of the stability limit state (SLS), a linear elastic material behavior of the subsoil is considered. In contrast, for the design of the ultimate limit state (ULS), a rigid-plastic material behavior of the subsoil is considered. This issue of spread foundations is explained in Figure 3.2.
According to the technical standards and regulations, the following incidents have to be analyzed [8–11]:
Figure 3.2 Load-settlement curve for spread foundations.
If spread foundations are located in the area of embankments, an analysis of the slope failure is necessary. Every possible failure mechanism (slip circles, complex rupture mechanisms) has to be considered [12–14].
In simple cases and under certain conditions, the geotechnical analysis of spread foundations can be done on the basis of standard table values. The standard table values take into account the analysis of safety against failure and harmful settlements [10].
The knowledge of the distribution of the contact pressure is the basis for the analysis of spread foundations. The following calculation procedures are available [15,16].
The distribution of the contact pressure under rigid foundations according to Boussinesq (a) offers theoretically infinitely large tensions at the edge of the foundation, which cannot arise because of transfer processes in the subsoil under the foundation. This method is applicable only in simple cases.
The simplest procedure is the stress trapeze method (b), because there is only a linear distribution of stresses assumed. The distribution of the contact pressure as a consequence of the stress trapeze method is a useful approach when using small foundations and small foundation depths.
The subgrade reaction modulus method (c) and the stiffness modulus method (d) are suitable, if the foundation depth is big. It can be used for single, strip, and raft foundations. Using the subgrade reaction modulus method, the subsoil is considered as a system of independent springs. A uniform load leads to a uniform settlement with no settlement trough. Using the stiffness modulus method, the subsoil is considered as an elastic half-space with a system of connected springs. A uniform load leads to a settlement trough. The stiffness modulus method leads to the most realistic distribution of the contact pressure.
The calculation methods (a) to (d) are approximate solutions to determine the distribution of the contact pressure below a spread foundation. These methods are usually sufficient for the analysis. The most realistic distribution of the contact pressure is given by numerical analysis because the stiffness of the structure as well the nonlinear material behavior of the subsoil can be considered.
The distribution of the contact pressure depends on the stiffness of the foundation as well as the relation between load and the stability of the sub-soil [18]. The potential distributions of the contact pressure are shown in Figure 3.3. Case (a) shows the distribution of the contact pressure when the bearing capacity is exploited poorly. When the load approaches to the bearing capacity two different failure mechanisms may occur. In case (b) the load leads to a plastic hinge inside the foundation which causes a redistribution of the contact pressure. In this case the bearing capacity of the foundation depends on the rotation capacity of the plastic hinge. In case (c) the load leads to a redistribution of the contact pressure to the center of the foundation which leads to a base failure.
If the foundation has no sufficient ductility, a brittle failing follows in excess of the internal load-bearing capacity, for example, punching. A redistribution of the contact pressure will not take place.
The assumption of a constant distribution of the contact pressure leads to results on the safe side for analysis of the ULS. For analysis of the SLS, the assumption of a constant distribution of the contact pressure leads to results on the unsafe side.
Figure 3.4 shows the settlement trough, the distribution of the contact pressure, and the curve of the moment, depending on the load. With an increasing load, the constant settlements under the foundation increase strongly in the center. At the same time, the contact pressure, which is concentrated in the border area, is shifted to the center of the foundation. The bending moments are concentrated under the load.
Figure 3.3 Distribution of the contact pressure under single foundations. (a) Elastic behavior of the foundation and the soil; (b) Plastic hinge in the foundation; (c) Base failure. (From Katzenbach, et al., Baugrund-Tragwerk-Interaktion. Handbuch für Bauingenieure: Technik, Organisation und Wirtschaftlichkeit. Springer-Verlag, Heidelberg, Germany, 1471–1490, 2012.)
For the determination of the internal force variable, the contact pressure, which depends on the proportion of the structure stiffness to the stiffness of the subsoil, needs to be analyzed.
Figure 3.4 Qualitative progression of deformations and stresses of a single foundation in dependency of its loading. (a) Deformation; (b) contact pressure; (c) bending moment. (From Katzenbach, et al., Baugrund-Tragwerk-Interaktion. Handbuch für Bauingenieure: Technik, Organisation und Wirtschaftlichkeit. Springer-Verlag, Heidelberg, Germany, 1471–1490, 2012.)
Figure 3.5 Distribution of the contact pressure for limp (a) and rigid (b) spread foundations.
K ≥ 0.1 |
Rigid foundation |
0.001 ≤ K < 0.1 |
Intermediate area |
K < 0.001 |
Limp foundation |
For limp spread foundations, the distribution of the contact pressure correspondents to the load distribution. For rigid foundations a nonlinear distribution of the contact pressure with high edge stresses arises (Figure 3.5). The differentiation between limp and rigid foundations is defined by the system rigidity K according to Kany, which is a value for the assessment of the interactions between the structure and the foundation (Equation 3.1). The differentiation is stated in Table 3.1 [16,21]. The system rigidity K is determined according to Equation 3.2. It is determined by the component height h, the length l, and the modulus of elasticity of the building material EB, which is founded in the elastic isotropic half-space (Figure 3.6) [16–20]:
where:
EB |
= modulus of elasticity of the structure [kN/m2] |
IB |
= geometrical moment of inertia of the spread foundation [m4] |
Es |
= oedometric modulus of the subsoil [kN/m2] |
b |
= width of the spread foundation [m] |
l |
= length of the spread foundation [m] |
h |
= height of the spread foundation [m] |
Figure 3.6 Dimensions for determining the rigidity of the system.
Circular spread foundations with a component height h and a diameter d have a system rigidity K in accordance with
For the calculation of spread foundations, normally only the rigidity of the foundation component is used to consider the rigidity of the building. The rigidity of the rising construction is considered only in special cases.
For limp spread foundations (K < 0.001), the settlement at the characteristic point is the same as the settlement of a rigid spread foundation (Figure 3.7). The characteristic point for rectangular foundations is at 0.74 of the half-width outward from the center. For circular spread foundations, the characteristic point is at 0.845 of the radius outward from the center.
Regardless of the load position and size, rigid spread foundations keep their forms. The distribution of the contact pressure has a strong nonlinear behavior with big edge stresses (Figure 3.5).
Figure 3.7 Characteristic point of a rectangular spread foundation.
For rigid spread foundations, single foundations, and strip foundations with a big thickness, the distribution of the contact pressure can be determined according to Boussinesq, or with the stress trapeze method [16]. Otherwise, more detailed studies or sufficient conservative assumptions that are “on the safe side” become necessary.
Based on the assumption that the subsoil is modeled as an elastic isotropic half-space, in the year 1885, Boussinesq developed equations that can be used for rigid spread foundations in simple cases [17].
The distribution of the contact pressure under a rigid strip foundation with a width b is given by Equation 3.4 (Figure 3.8). For an eccentric load with an eccentricity e, Borowicka enhanced the following equations [22]:
Figure 3.8 Distribution of the contact pressure under rigid foundations according to Boussinesq.
Figure 3.9 Distribution of the contact pressure under rigid foundations as a result of centric loads on elastic isotropic half-space
For circular and rectangular rigid spread foundations, the distribution of the contact pressure can be determined using Figure 3.9.
At the edge of spread foundations, infinitely large stresses arise. Due to the ultimate bearing capacity, imposed by the shear strength of the subsoil, these peak stresses cannot occur. The subsoil plasticizes at the edges of the foundations and the stresses shift to the center of the foundations [23].
The stress trapeze method is a statically defined method, and it is the oldest to determine the distribution of the contact pressure. The stress trapeze method is based on the beam theory of elastostatic principles.
The distribution of the contact pressure is determined by the equilibrium conditions ΣV and ΣM, without considering deformations of the building or the subsoil interactions, respectively. Subsoil is simplified with linear elastic behaviour for calculation. Even large edge stresses are theoretically possible. The detection of the reduction of stress peaks due to plasticization is not immediately possible. All considerations are based on the assumption of Bernoulli stating that the cross-sections remain plane.
The force V is the resultant of the applied load, self-weight and buoyancy force. The resultant of the forces and the contact pressures have the same line of influence and the same value but point in opposite directions. To determine the distribution of the contact pressure of an arbitrarily spread foundation, Equation 3.7 is used. For the axes of coordinates, an arbitrarily rectangular coordinate system is used, where the zero point corresponds with the center of gravity of the subface (Figure 3.10) [24].
Figure 3.10 Coordinate system for the contact pressure (stress trapeze method).
If the x- and the y-axis are the main axes of the coordinate system, the centrifugal moment Ixy = 0. Equation 3.7 is simplified to the following Equation 3.8. If the resultant force V acts at the center of gravity of the subface, the torques Mx = My = 0. The result is a constant distribution of the contact pressure according to Equation 3.9.
If the eccentricity of the resulting forces V is too large, theoretically tensile stresses occur, which are not absorbed by the system subsoilsuperstructure. An open gap occurs. In this case, Equations 3.7 through 3.9 are not applicable, and the determination of the maximum contact pressure is performed according to the following equation in conjunction with Table 3.2:
0.32 |
3.70 |
3.93 |
4.17 |
4.43 |
4.70 |
4.99 |
|
|
|
|
|
|
|
|
|
|
|
0.30 |
3.33 |
3.54 |
3.75 |
3.98 |
4.23 |
4.49 |
4.78 |
5.09 |
5.43 |
|
|
|
|
|
|
|
|
0.28 |
3.03 |
3.22 |
3.41 |
3.62 |
3.84 |
4.08 |
4.35 |
4.63 |
4.94 |
5.28 |
5.66 |
|
|
|
|
|
|
0.26 |
2.78 |
2.95 |
3.13 |
3.32 |
3.52 |
3.74 |
3.98 |
4.24 |
4.53 |
4.84 |
5.19 |
5.57 |
|
|
|
|
|
0.24 |
2.56 |
2.72 |
2.88 |
3.06 |
3.25 |
3.46 |
3.68 |
3.92 |
4.18 |
4.47 |
4.79 |
5.15 |
5.55 |
|
|
|
|
0.22 |
2.38 |
2.53 |
2.68 |
2.84 |
3.02 |
3.20 |
3.41 |
3.64 |
3.88 |
4.15 |
4.44 |
4.77 |
5.15 |
5.57 |
|
|
|
0.20 |
2.22 |
2.36 |
2.50 |
2.66 |
2.82 |
2.99 |
3.18 |
3.39 |
3.62 |
3.86 |
4.14 |
4.44 |
4.79 |
5.19 |
5.66 |
|
|
0.18 |
2.08 |
2.21 |
2.35 |
2.49 |
2.64 |
2.80 |
2.98 |
3.17 |
3.38 |
3.61 |
3.86 |
4.15 |
4.47 |
4.84 |
5.28 |
|
|
0.16 |
1.96 |
2.08 |
2.21 |
2.34 |
2.48 |
2.63 |
2.80 |
2.97 |
3.17 |
3.38 |
3.62 |
3.88 |
4.18 |
4.53 |
4.94 |
5.43 |
|
0.14 |
1.84 |
1.96 |
2.08 |
2.21 |
2.34 |
2.48 |
2.63 |
2.79 |
2.97 |
3.17 |
3.39 |
3.64 |
3.92 |
4.24 |
4.63 |
5.09 |
|
0.12 |
1.72 |
1.84 |
1.96 |
2.08 |
2.21 |
2.34 |
2.48 |
2.63 |
2.80 |
2.98 |
3.18 |
3.41 |
3.68 |
3.98 |
4.35 |
4.78 |
|
0.10 |
1.60 |
1.72 |
1.84 |
1.96 |
2.08 |
2.21 |
2.34 |
2.48 |
2.63 |
2.80 |
2.99 |
3.20 |
3.46 |
3.74 |
4.08 |
4.49 |
4.99 |
0.08 |
1.48 |
1.60 |
1.72 |
1.84 |
1.96 |
2.08 |
2.21 |
2.34 |
2.48 |
2.64 |
2.82 |
3.02 |
3.25 |
3.52 |
3.84 |
4.23 |
4.70 |
0.06 |
1.36 |
1.48 |
1.60 |
1.72 |
1.84 |
1.96 |
2.08 |
2.21 |
2.34 |
2.49 |
2.66 |
2.84 |
3.06 |
3.32 |
3.62 |
3.98 |
4.43 |
0.04 |
1.24 |
1.36 |
1.48 |
1.60 |
1.72 |
1.84 |
1.96 |
2.08 |
2.21 |
2.35 |
2.50 |
2.68 |
2.88 |
3.13 |
3.41 |
3.75 |
4.17 |
0.02 |
1.12 |
1.24 |
1.36 |
1.48 |
1.60 |
1.72 |
1.84 |
1.96 |
2.08 |
2.21 |
2.36 |
2.53 |
2.72 |
2.95 |
3.22 |
3.54 |
3.93 |
0.00 |
1.00 |
1.12 |
1.24 |
1.36 |
1.48 |
1.60 |
1.72 |
1.84 |
1.96 |
2.08 |
2.22 |
2.38 |
2.56 |
2.78 |
3.03 |
3.33 |
3.70 |
|
0.00 |
0.02 |
0.04 |
0.06 |
0.08 |
0.10 |
0.12 |
0.14 |
0.16 |
0.18 |
0.20 |
0.22 |
0.24 |
0.26 |
0.28 |
0.30 |
0.32 |
eb/b |
Historically, an interaction between soil and structure was taken into account for the first time by using the subgrade reaction modulus method. The prepared subgrade reaction in relation with the change of shape was formulated in the nineteenth century by Winkler [25]. It was created for the design of railway tracks.
According to Winkler, the elastic model of the subsoil, which is also called half-space of Winkler, is a spring model, where at any point the contact pressure σ0 is proportional to the settlement s (Equation 3.11). The constant of proportionality ks is called the subgrade reaction modulus. The subgrade reaction modulus can be interpreted as a spring due to the linear mechanical approach for the subsoil behavior (Figure 3.11). However, this method does not consider the interactions between the independent, free-movable vertical springs.
where:
σ0 |
= contact pressure [kN/m2] |
s |
= settlement [m] |
ks |
= subgrade reaction modulus [kN/m3] |
Using the beam-bending theory, it is possible to describe the curve of the bending moment for an arbitrary, infinitely long and elastic strip foundation with the width b, which is founded on the half-space of Winkler.
The curve of the bending moment of the strip foundation with the bending stiffness Eb × I is given by
The double differentiation of Equation 3.12 results in
Figure 3.11 Spring model for the subgrade reaction modulus method.
The action q(x) corresponds to the contact pressure σ0(x), which can be described by
With the elastic length L given as
and the elimination of s(x), Equation 3.16 follows. For a large number of boundary conditions, Equation 3.16 can be solved. For an infinite long strip foundation, the distribution of the contact pressure σ0(x), the distribution of the bending moment M(x), and the distribution of the shear forces result according to Equations 3.17 through 3.19.
The subgrade reaction modulus is not a soil parameter. It depends on the following parameters:
The subgrade reaction modulus method does not take into account the influence of neighboring contact pressures. It is therefore mainly suitable for the calculation of slender, relatively limp spread foundations with large column distances. With the subgrade reaction modulus method, it is not possible to determine settlements beside the spread foundation (Figure 3.12).
Figure 3.12 Distribution of the settlements according to the subgrade reaction modulus method.
The stiffness modulus method according to Ohde (1942) describes the soil– structure interaction more accurately than the subgrade reaction modulus method, because the influence of adjacent contact pressures is considered on the settlement of an arbitrary point of the spread foundation [19,26]. In the stiffness modulus method, the bending moment of the linear elastic modeled spread foundation is linked with the bending moment of the linear elastic, isotropic modeled settlement trough. The same deformations arise.
Figure 3.13 represents the distribution of the settlement of a spread foundation according to the stiffness modulus method.
In geotechnical engineering practice, spread foundations with complex load situations and geometric boundary conditions are normally examined using computer programs. For most cases, no closed solutions are available for the statically indeterminate system of equations.
The assumption of infinite elastic subsoil has the consequence that theoretically infinite large stress peaks result at the edge of the spread foundation. Due to the plasticizing effect of the subsoil, these stress peaks do not occur in reality. Powerful computer programs consider this basic soil mechanical behavior.
In the following section the geotechnical analysis for stability and serviceability of spread foundations are defined according to the currently valid technical regulations EC 7.
Figure 3.13 Distribution of the settlements according to the stiffness modulus method.
The analysis of the stability includes
The analysis of the serviceability includes
Up to now, the analysis of safety against loss of balance because of overturning was done by applying the resultant of the forces into the second core width. That means that the lower surface of the spread foundation has only a small part with an open gap. This approach is described in [27,28]. Thus, a resulting force in the first core width creates a compressive stress over the entire lower surface of the spread foundation.
According to the current technical regulations, the analysis of safety against loss of balance because of overturning is based on a principle of the rigid body mechanics. The destabilizing and stabilizing forces are compared based on a fictional tilting edge at the edge of the spread foundation:
The design value of the destabilizing force is estimated according to Equation 3.21, and the design value of the stabilizing action is estimated according to Equation 3.22:
In reality, the position of the tilting edge depends on the rigidity and the shear strength of the subsoil. With a decreasing rigidity and decreasing shear strength, the tilting edge moves to the center of the lower surface of the spread foundation.
Therefore, this analysis itself is not sufficient. It was complemented by the analysis of the limitation of the open gap, which is defined for the serviceability limit state. According to [10], the resultant force of the permanent loads has to be applied into the first core width and the resultant force of the variable loads has to be applied into the second core width (Figure 3.21).
The analysis of safety against sliding (limit state GEO-2) is calculated according to Equation 3.23. The forces parallel to the lower surface of the spread foundation have to be smaller than the total resistance, consisting of slide resistance and passive earth pressure. If the passive earth pressure is considered, the serviceability limit state has to be verified regarding the horizontal displacements.
where:
The sliding resistance is determined according to the three following cases:
Vk | = characteristic value of the vertical loadings [kN] |
δ | = characteristic value of the angle of base friction [°] |
where:
Vk |
= characteristic value of the vertical loadings [kN] |
φ′ |
= characteristic friction angle for the subsoil under the spread foundation [°] |
A |
= area of the load transmission [m2] |
c′ |
= characteristic value of the cohesion of the subsoil [kN/m2] |
where:
A |
= Area of the load transmission [m2] |
cu |
= Characteristic value of the undrained cohesion of the sub-soil [kN/m2] |
For spread foundations that are concreted in situ, the characteristic value of the angle of base friction δ is the same as the characteristic value of the friction angle φ′ of the soil. For prefabricated spread foundation elements the characteristic value of the angle of base friction δ should be set to 2/3 φ′. The characteristic value of the angle of base friction should be δ ≤ 35°.
A passive earth pressure can be considered if the spread foundation is deep enough. Due to horizontal deformations, the passive earth pressure should be limited to 50% of the possible passive earth pressure. Basically, it must be verified whether the passive earth pressure exists during all possible stages in the construction and the service phase of the foundation.
The analysis of safety against base failure is guaranteed if the design value of the bearing capacity Rd is bigger than the design value of the active force Vd. Rd is calculated according to Equation 3.27. The principle scheme of a bearing failure of a spread foundation is shown in Figure 3.14.
The resistance of the bearing capacity is determined by the soil properties (density, shear parameters), the dimensions and the embedment depth of the spread foundation. Detailed information can be found in the incidental standard [29,30]. The characteristic resistance of the bearing capacity Rn,k is calculated analytically with a trinomial equation, which is based on the moment equilibrium of the failure figure of the bearing capacity in ideal plastic, plane deformation state [31]. The trinomial equation of the bearing capacity considers the width b of the foundation, the embedment depth d of the foundation and the cohesion c′ of the subsoil. All three aspects have to be factorized with the bearing capacity factors Nb, Nd, and Nc:
Figure 3.14 Bearing failure figure of a strip foundation 1, Reinforced wall; 2, area; 3, resulting contact pressure; 4, cellar floor; 5, sliding surface, the form depends on the angle of friction φ; 6, passive Rankine-zone of the failure body; 7, active Rankine-zone of the failure body; 8, Prandtl-zone of the failure body.
where:
The density γ1 describes the density of the subsoil above the foundation level. The density γ2 describes the density of the subsoil underneath the foundation level. The bearing capacity factors Nb, Nd, and Nc consider the following boundary conditions:
The parameters of the bearing capacity factors Nb0, Nd0, Nc0 depend on the angle of friction of the subsoil φ’ and are calculated according to Table 3.3.
Foundation width Nb0 |
Foundation depth Nd0 |
Cohesion Nc0 |
---|---|---|
(Nd0–1) tan φ |
|
|
Floor plan |
νb |
νd |
νc (φ ≠ 0) |
νc (φ = 0) |
---|---|---|---|---|
Strip |
1.0 |
1.0 |
1.0 |
1.0 |
Rectangle |
|
|
|
|
Square/Circle |
0.7 |
1 + sin φ |
|
1.2 |
The shape parameters νb, νd, νc take into account the geometric dimensions of the spread foundation. For the standard applicable geometry, the shape parameters are summarized in Table 3.4.
If eccentric forces have to be considered the base area has to be reduced. The resulting load has to be in the center of gravity. The reduced dimensions a′ and b′ are calculated according to Equations 3.29 and 3.30. Basically applied, is a > b and a′ > b′, respectively. For spread foundations with open parts, the external dimensions may be used for the analysis, if the open parts are not bigger than 20% of the whole base area.
where
Forces Tk that are parallel to the foundation level are considered by the parameters ib, id, ic for the load inclination. The definition of the angle of the load inclination is shown in Figure 3.15. The determination of the parameters for the load inclination is shown in Tables 3.5 and 3.6. The orientation of the acting forces is determined by the angle ω (Figure 3.16). For a strip foundation ω = 90°.
Figure 3.15 Definition of the angle of the load inclination.
Direction |
ib |
id |
ic |
---|---|---|---|
δ > 0 |
(1 – tan δ)m + 1 |
(1 – tan δ)m |
|
δ < 0 |
|
|
ib |
id |
ic |
---|---|---|
Not necessary, because of φ = 0 |
1.0 |
|
An inclination of the landscape is considered by the parameters λb, λd, λc for landscape inclination. The parameters depend on the slope inclination β. The slope inclination has to be less than the angle of friction φ′ of the subsoil and the longitudinal axis of the foundation has to be parallel to the slope edge. The determination of the parameters for landscape inclination is shown in Figure 3.17 and Table 3.7.
Figure 3.16 Angle ω for an oblique acting load.
Figure 3.17 Eccentric, oblique loaded strip foundation on a slope.
Case |
λb |
λd |
λc |
---|---|---|---|
φ > 0 |
(1 – 0.5 tanβ)6 |
(1 – tanβ)1,9 |
|
φ = 0 |
— |
1.0 |
1–0.4 tanβ |
Case |
ξb |
ξd |
ξc |
---|---|---|---|
φ > 0 |
e−0.045 · α · tan φ |
e−0.045 · α · tan φ |
e−0.045 · α · tan φ |
φ = 0 |
— |
1.0 |
1−0.0068α |
The base inclination is considered by the parameters ξb, ξd, ξc for the base inclination (Table 3.8), which depend on the angle of friction φ’ of the subsoil and the base inclination α of the spread foundation. The definition of the base inclination is shown in Figure 3.18. The angle of the base inclination α is positive, if the failure body forms out in the direction of the horizontal forces. The angle of the base inclination α is negative, if the failure body forms in the opposite direction. In cases of doubt, both failure bodies have to be investigated.
The direct application of the defined equations is only possible if the sliding surface is formed in one soil layer. For layered soil conditions, it is permissible to calculate with averaged soil parameters if the values of the individual angles of friction do not vary more than 5° of the arithmetic average. In this case, the individual soil parameters may be weighted according to their influence on the shear failure resistance. The weighting is as follows.
Figure 3.18 Angle of the base inclination α.
Authoritative for the sliding surface is the average of the angle of friction φ. To determine whether the failure body has more than one layer, it is recommended to define the failure body according to Equation 3.32 through 3.38 (Figure 3.19). For simple cases (α = β = δ = 0), the Equations 3.39 through 3.42 have to be applied.
Figure 3.19 Determination of the failure body.
where:
where
For spread foundations at slopes, the foundation depth d′ (Equation 3.43) and the parameters λb, λd, λc for landscape inclination have to be considered (Figure 3.20). In addition, it is necessary to carry out a comparative calculation with β = 0 and d′ = d. The smaller resistance is the basis of the analysis of the bearing capacity regarding base failure.
Figure 3.20 Spread foundation on a slope.
The analysis of safety against buoyancy (limit state UPL) is performed using Equation 3.44. This equation is the proof that the net weight of the structure is big enough compared to the buoyant force of the water. Shear forces (friction forces at the side) can only be considered if the transmission of the forces is ensured. Acting shear forces Tk may be
where:
Gdst,k |
= permanent destabilizing vertical load (buoyancy) |
γG,dst |
= partial safety factor for permanent destabilizing load |
Qdst,rep |
= representative variable destabilizing vertical load |
γQ,dst |
= partial safety factor for variable destabilizing load |
Gstb,k |
= permanent stabilizing load |
γG,stb |
= partial safety factor for permanent stabilizing load |
Tk |
= shear force |
The smallest possible horizontal earth pressure min Eah,k has to be used. For the design situation BS-P and BS-T, the adjustment factor is ηz = 0.80. For the design situation BS-A, the adjustment factor is ηz = 0.90. Only in justified cases can cohesion be taken into account, but it has to be reduced by the adjustment factors. For permanent structures, it has to be determined that in design situation BS-A, the safety against buoyancy is given without any shear forces Tk.
Generally, the serviceability limit states refer to absolute deformations and displacements as well as differential deformations. In special cases, for example, time-dependent material behavior displacement rates have to be considered.
For the analysis of foundation rotation and limitation of the open gap, the resultant of the dead loads has to be limited into the first core width, which means that an open gap does not occur. The first core width for rectangular spread foundations can be determined according to Equation 3.47. For circular spread foundations Equation 3.48 is used. Furthermore, it should be guaranteed that the resultant of the permanent loads and the variable loads are in the second core width, so an open gap cannot occur across the center line of the spread foundation. The second core width for rectangular layouts can be determined according to Equation 3.49. For circular spread foundations Equation 3.50 is used. Figure 3.21 shows the first and the second core width for a rectangular spread foundation.
Figure 3.21 Limitation of the eccentricity.
For single and strip foundations, which are founded on medium-dense, non-cohesive soils and stiff cohesive soils, respectively, no incompatible distortions of the foundation can be expected if the acceptable eccentricity is observed.
The analysis of foundation rotation and limitation of the open gap is mandatory according to [10], if the analysis of safety against loss of balance because of overturning is carried out by using one edge of the spread foundation as a tilting edge.
Generally, for spread foundations the analysis of horizontal displacement is observed, if:
If these arguments are not true, it is necessary to analyze the possible horizontal displacements. Permanent loads and variable loads, as well as infrequent or unique loads, have to be considered.
The determinations for settlements of spread foundations are conducted in accordance with [32]. Normally, the influence depth of the contact pressure is between z = b and z = 2b.
Due to the complex interaction between the subsoil and the construction, it is difficult to provide information about the acceptable settlements or differential settlements for constructions [33]. Figure 3.22 indicates the damage factors for the angular distortion as a result of settlements [33–35].
Figure 3.22 Damage criterion.
Regarding the tilting of high-rise structures, the analysis of safety against inclination has to check that the occurring tilting is harmless for the structure [33]. The analysis for rectangular spread foundations is performed according to Equation 3.51. The analysis for circular spread foundations is performed according to Equation 3.52.
In Equations 3.51 and 3.52:
Em = Modulus for the compressibility of the subsoil
hs = Height of the center of gravity above the foundation level
fr and fy = Tilting coefficients
Vd = Design value of the vertical loads
The simplified analysis of spread foundations in standard cases consists of a simple comparison between the base resistance σR,d and the contact pressure σE,d (Equation 3.53). For spread foundations with the area A = a × b or A′ = a′ × b′, the analysis of safety against sliding and base failure, as well as the analysis of the serviceability limit state, can be applied in standard cases. These standard cases include:
The design values of the contact pressure σR,d are based on the combined examination of the base failure and the settlements. If only the SLS is analyzed, the admissible contact pressure increases with an increasing width of the spread foundation. If only the ULS is analyzed, the admissible contact pressure decreases with an increasing width of the spread foundation. Figure 3.23 shows the two fundamental demands for an adequate analysis against base failure (ULS) and the analysis of the settlements (SLS). For foundation widths that are bigger than the width bs, the acceptable contact pressure decreases because of settlements.
The design values of the contact pressure σR,d for simplified analysis of strip foundations are specified in tables. The tabular values can also be used for single foundations [10,37,38].
If the foundation level is more than 2 m below the surface on all sides, the tabular values can be raised. The raise can be 1.4 times the unloading due to the excavation below a depth of ≥2 m under the surface.
The settlement values in the tables refer to detached strip foundations with a central loading (no eccentricity). If eccentric loads occur, the serviceability has to be analyzed. For the application of the current table values, it is essential to notice that in earlier editions of these tables, characteristic values were given [10].
The simplified analysis of the ULS and SLS of strip foundations in non-cohesive soils considers the design situation BS-P. For the design situation BS-T the tabular values are “on the safe side”. The tabular values are applicable for vertical loads. Intermediate values may be interpolated linearly. For eccentric loads the tabular values may be extrapolated if width b′ < 0.50 m. There must be a distance between the lower surface of the foundation and the groundwater level. The distance must be bigger than the width b or b′ of the foundation. For the application of the tables for non-cohesive soils the requirements in Table 3.9 must be fulfilled. The short forms of the soil groups are explained in Table 3.10.
Figure 3.23 Maximum contact pressure σR,d taking into account the stability (ULS) and serviceability (SLS).
Soil group according to DIN 18196 |
Coefficient of uniformity according to DIN 18196 Cu |
Compactness according to DIN 18126 D |
Compression ratio according to DIN 18127 DPr |
Point resistance of the soil penetrometer qc [MN/m2] |
---|---|---|---|---|
SE, GE, SU, GU, ST, GT |
≤ 3 |
≥ 0.30 |
≥ 95% |
≥ 7.5 |
SE, SW, SI, GE GW, GT, SU, GU |
> 3 |
≥ 0.45 |
≥ 98% |
≥ 7.5 |
The coefficient of uniformity Cu describes the gradient of the grain size distribution in the area of passing fractions of 10% and 60% and it is determined according to Equation 3.54 [39]. According to [40], the compactness D describes whether the subsoil is loose, medium dense, or dense. The compactness D is determined by the porosity n, according to Equation 3.55. The compression ratio Dpr is the relation between the proctor density ρpr (density at optimal water content) and the dry density ρd [41]. The compression ratio is calculated using Equation 3.56.
Short form according to DIN 18196 |
Long form according to DIN 18196 in German |
Long form according to DIN 18196 in English |
---|---|---|
SE |
Sand, enggestuft |
Sand with small grain size distribution |
SW |
Sand, weitgestuft |
Sand with a wide spreaded grain size distribution |
SI |
Sand, intermittierend gestuft |
Sand with an intermittent spreaded grain size distribution |
GE |
Kies, enggestuft |
Gravel with small grain size distribution |
GW |
Kies, weitgestuft |
Gravel with a wide spreaded grain size distribution |
ST |
Sand, tonig (Feinkornanteil: 5–15%) |
Sand, clayey (fine fraction: 5–15%) |
SU |
Sand, schluffig (Feinkornanteil: 5–15%) |
Sand, silty (fine fraction: 5–15%) |
GT |
Kies, tonig (Feinkornanteil: 5–15%) |
Gravel, clayey (fine fraction: 5–15%) |
GU |
Kies, schluffig (Feinkornanteil: 5–15%) |
Gravel, clayey (fine fraction: 5–15%) |
For simplified analysis of strip foundations Table 3.11 shows the permissible design values of the contact pressure σR,d for non-cohesive soils taking into account an adequate safety against base failure. If the settlement has to be limited additionally, Table 3.12 has to be applied. For the purpose of Table 3.12, the settlements are limited to 1–2 cm.
The permissible design values of the contact pressure σR,d for strip foundations in non-cohesive soils with the minimum width b ≥ 0.50 m and the minimum embedment depth d ≥ 0.50 m can be increased as follows:
Smallest embedment depth of the foundation [m] | Design value of the contact pressure σR,d [kN/m2] in dependence of the foundation width b resp. b′ | |||||
---|---|---|---|---|---|---|
0.50 m | 1.00 m | 1.50 m | 2.00 m | 2.50 m | 3.00 m | |
0.50 | 280 | 420 | 560 | 700 | 700 | 700 |
1.00 | 380 | 520 | 660 | 800 | 800 | 800 |
1.50 | 480 | 620 | 760 | 900 | 900 | 900 |
2.00 | 560 | 700 | 840 | 980 | 980 | 980 |
For buildings with an embedment depth 0.30 m ≤ d ≤ 0.50 m and foundation width b resp. b′ ≥ 0.30 m | 210 |
Smallest embedment depth of the foundation [m] | Design value of the contact pressure σR,d[kN/m2] in dependence of the foundation width b resp. b′ | |||||
---|---|---|---|---|---|---|
0.50 m | 1.00 m | 1.50 m | 2.00 m | 2.50 m | 3.00 m | |
0.50 | 280 | 420 | 460 | 390 | 350 | 310 |
1.00 | 380 | 520 | 500 | 430 | 380 | 340 |
1.50 | 480 | 620 | 550 | 480 | 410 | 360 |
2.00 | 560 | 700 | 590 | 500 | 430 | 390 |
For buildings with an embedment depth 0.30 m ≤ d ≤ 0.50 m and foundation width b resp. b′ ≥ 0.30 m | 210 |
The permissible design values of the contact pressure for strip foundations in non-cohesive soils in Table 3.11 (even increased and/or reduced due to horizontal loads) have to be reduced if groundwater has to be considered:
Soil group according to DIN 18196 | Coefficient of uniformity according to DIN 18196 Cu | Compactness according to DIN 18126 D | Compression ratio according to DIN 18127 DPr | Point resistance of the soil penetrometer qc [MN/m2] |
---|---|---|---|---|
SE, GE, SU, GU, ST, GT | ≤3 | ≥0.50 | ≥98% | ≥15 |
SE, SW, SI, GE GW, GT, SU, GU | >3 | ≥0.65 | ≥100% | ≥15 |
The permissible design values of the contract pressure σR,d in Table 3.12 can only be used if the design values in Table 3.11 (even increased and/or reduced due to horizontal loads and/or groundwater) are bigger.
The permissible design values of the contact pressure σR,d for strip foundations in non-cohesive soils shown in Table 3.11 (even increased and/or reduced due to groundwater) need to be reduced for a combination of characteristic vertical (Vk) and horizontal (Hk) loads as follows:
The design values of the contact pressure shown in Table 3.12 can only be applied if the design values σR,d shown in Table 3.11 (even increased and/or reduced due to groundwater) are bigger.
The simplified analysis of the ULS and SLS of strip foundations in cohesive soils is for the design situation BS-P. For the design situation BS-T, the tabular values are “on the safe side.” The tabular values are applicable for vertical and inclined loads. Intermediate values may be interpolated linearly. The tables are given for different types of soil. The short forms of the soil groups are explained in Table 3.10. If the Tables 3.14 through 3.17 are used, settlements of 2–4 cm can be expected. In principle, the Tables 3.14 through 3.17 are only applicable for soil types with a granular structure that may not collapse suddenly.
The design values σR,d for strip foundations in cohesive soil shown in Tables 3.14 through 3.17 (even reduced due to foundation width b > 2 m) may be increased by 20% if the aspect ratio is a/b < 2 resp. a′/b′ < 2.
Silt (UL according to DIN 18126) consistency: Solid to semisolid |
|
---|---|
Smallest embedment depth of the foundation [m] |
Design values σR,d of the contact pressure [kN/m2] |
0.50 |
180 |
1.00 |
250 |
1.0 |
310 |
2.00 |
350 |
Unconfined compressive strength qu,k [kN/m2] |
120 |
Mixed soils (SU*, ST, ST*, GU*, GT* according to DIN 18196) |
|||
---|---|---|---|
Smallest embedment depth of the foundation [m] |
Design values σR,d of the contact pressure [kN/m2] |
||
Consistency |
|||
Stiff |
Semi-solid |
Solid |
|
0.50 |
210 |
310 |
460 |
1.00 |
250 |
390 |
530 |
1.50 |
310 |
460 |
620 |
2.00 |
350 |
520 |
700 |
Unconfined compressive strength qu,k [kN/m2] |
120–300 |
300–700 |
>700 |
Clay, silty soils (UM, TL, TM according to DIN 18196) |
|||
---|---|---|---|
Smallest embedment depth of the foundation [m] |
Design values σR,d of the contact pressure [kN/m2] |
||
Consistency |
|||
Stiff |
Semi-solid |
Solid |
|
0.50 |
170 |
240 |
490 |
1.00 |
200 |
290 |
450 |
1.50 |
220 |
350 |
500 |
2.00 |
250 |
390 |
560 |
Unconfined compressive strength qu,k [kN/m2] |
120–300 |
300–700 |
>700 |
Clay, silty soils (UM, TL, TM according to DIN 18196) |
|||
---|---|---|---|
Smallest embedment depth of the foundation [m] |
Design values σR,d of the contact pressure [kN/m2] |
||
Consistency |
|||
Stiff |
Semi-solid |
Solid |
|
0.50 |
130 |
200 |
280 |
1.00 |
150 |
250 |
340 |
1.50 |
180 |
290 |
380 |
2.00 |
210 |
320 |
420 |
Unconfined compressive strength qu,k [kN/m2] |
120–300 |
300–700 |
>700 |
The design values σR,d for strip foundations in cohesive soil shown in Tables 3.14 through 3.17 (even increased due to the aspect ratio) have to be reduced by 10% per meter at foundation width b = 2–5 m. For foundations with a width b > 5 m the ULS and the SLS have to be checked separately according to the classic soil mechanical analysis.
In the last decades, increasing population density worldwide has led to the construction of more and higher high-rise buildings. Until 1960, in Frankfurt am Main, Germany, buildings with 10–15 storeys were considered to be high-rise. In 1961, the first building with 20 storeys was constructed, and in 1969 the first Commerzbank Tower with 30 storeys and a height of 130 m was completed. In the 1970s and early 1980s, several other skyscrapers were built with heights of 150–180 m. All were founded in the very settlement-active Frankfurt Clay. The experiences in Frankfurt am Main show, that the final settlements of a spread foundation can be 1.7 to 2.0 times the settlements at the end of the construction phase. Final settlements of 15–35 cm occurred [42,43].
Nearly all high-rise buildings founded on spread foundations in Frankfurt Clay have differential settlements, which lead to a tilting of the superstructures [43]. A statistical evaluation of the measurements indicates that this tilting is up to 20–30% of the average settlement, even if the foundation is loaded centrically [44]. The differential settlements result from the inhomogeneity of the Frankfurt subsoil.
The high-rise building complex of the Zürich Assurance Company in Frankfurt am Main, Germany, was constructed from 1959 to 1963. It consists of two towers 63 m and 70 m high, respectively, and an annex building up to eight storeys. The whole complex has two sublevels and is founded on a spread foundation. The foundation depth is 7 m below the surface. The ground view is shown in Figure 3.24.
The soil and groundwater conditions are representative for Frankfurt am Main. At the surface are fillings and quaternary sands and gravel. At a depth of about 7 m below the surface, begins the tertiary Frankfurt Clay, which consists of alternating layers of stiff to semisolid clay and limestone. At a depth of 67 m below the surface follows the Frankfurt Limestone. The groundwater level is about 5–6 m below the surface.
The measured settlements at the end of the construction of the super-structure are about 60% of the final settlements (Figure 3.25). After the end of the construction, the settlement rate decreased due to the consolidation process. About 5 years after the end of the construction, the settlements come to an end at about 8.5–9.5 cm.
Figure 3.24 Ground view of the high-rise building complex of Zürich Assurance.
Figure 3.25 Measured settlements.
In the years 2001 and 2002 the high-rise building complex was deconstructed. In its place now is the Opernturm, with a height of 177 m [45,46].
The high-rise Westend Gate building (former name: Senckenberganlage) in Frankfurt am Main, Germany, was constructed from 1972 to 1974 (Figure 3.26). It is 159 m high and is founded on a spread foundation system. The basement has three sublevels. The building is an office tower up to the 23rd floor. Above the office part is the Marriott Hotel. The soil and groundwater conditions are similar to the high-rise building complex of the Zürich Assurance.
Westend Gate is the high-rise building with the biggest settlements in Frankfurt am Main [47]. The measured settlements of the building were greater than 30 cm, caused by comparatively high contact pressures of 650 kN/m2. The raft foundations were only arranged under the high-rise building. The annex sublevels were founded on single foundations (Figure 3.27). For controlling the settlements and the differential settlements, expansion joints were arranged between the foundation elements and the superstructure. The expansion joints were closed after finishing the reinforcedconcrete cores. The flexible steel structure, which reaches from the third to the 23rd floor, was not damaged by the settlements and the differential settlements. The storeys above the 23rd floor were constructed with reinforcedconcrete cells with a comparatively high stiffness. Hydraulic jacks have been installed between the flexible steel construction and the stiff concrete cells. The hydraulic jacks balance the occurring settlements. Due to the long-term settlement behavior of the soil, several joints in the upper floors have been kept open until two years after the construction [47,48].
Figure 3.26 Westend Gate.
The Silver Tower (formerly Dresdner Bank) in Frankfurt am Main, Germany, is 166 m high and was constructed from 1975 to 1978 (Figure 3.28). The Silver Tower is constructed on a foundation raft with an average thickness of 3.5 m. The foundation level is 14 m deep under the surface. The soil and groundwater conditions are similar to the high-rise building complex of the Zürich Assurance.
Due to the eccentric loading, 22 pressure cushions were installed in the northwest under the foundation raft (Figure 3.29) [42,49]. The pressure cushions have a size of 5 m × 5 m and consist of soft rubber with a thickness of 3 mm. The tightness of the pressure cushions was checked before the installation. The cushions were filled initially with water. The pressures inside the cushions were regulated so only small differential settlements occurred. After the end of the construction and the adjustment of the high-rise building, the water in the cushions was replaced by mortar.
Figure 3.27 Construction phases.
Figure 3.28 Silver Tower (the left building; on the right: high-rise building Skyper).
Figure 3.29 Hydraulic devices to adjust the settlements.
The FBC is a 142 m high-rise building in Frankfurt am Main, Germany, which is founded on 3.5 m thick foundation raft. The foundation level is about 12.5 m below the surface. Figure 3.30 shows the high-rise building from the south. It was constructed from 1973 to 1980. The long construction time was due to a lack of investment during the oil crisis. The soil and groundwater conditions are similar to the high-rise building complex of the Zürich Assurance.
From the beginning of the construction, the settlements were measured for 5 years (Figure 3.31). The maximum final settlement was about 28 cm in the core area of the high-rise building [42]. About 1.5 years after construction ended, the settlements were about 70% of the final settlements. The differential settlements between the high-rise building and the adjacent buildings are between 9.5 cm and 20 cm (Figure 3.32). The tilting of the high-rise building is about 1:1350 [50].
Figure 3.30 Frankfurt Bureau Centre (FBC).
Figure 3.31 Measured settlements.
Figure 3.32 Cross section of the structure and measured settlements.
The twin towers of the Deutsche Bank in Frankfurt am Main, Germany, are 158 m high and were constructed from 1979 to 1984 (Figure 3.33). The towers are on a foundation raft with a size of 80 m × 60 m and a thickness of 4 m. The foundation level is about 13 m below the surface [51]. The soil and groundwater conditions are similar to the high-rise building complex of the Zürich Assurance.
The measured settlements are between 10 cm and 22 cm. Figure 3.34 shows the isolines of the settlements. To minimize the influence of the twin towers on the adjacent buildings, hydraulic jacks were installed (Figure 3.35). The possible regulation of the differential settlements by the hydraulic jacks was about ± 8 cm.
Figure 3.33 Twin Towers of Deutsche Bank.
Figure 3.34 Measured settlements.
Figure 3.35 Cross-section of the superstructure with hydraulic jacks.